Your documents basket contains 0 items
| Operating voltage | 110 V AC - 230 V AC |
| Frequency | 50 - 60 Hz |
| Installation height | 2 - 4 m |
| Minimum height | 1.7 m |
| Installation type | Ceiling installation |
| Colour | White |
| Power consumption | <0.4 W |
| Light measurement | Mixed light measurement |
| Setting range brightness | 10 - 3000 lx |
| Light switch-off delay | 10 s - 60 min |
| Stand-by time light | 0 s - 60 min / on |
| Stand-by brightness | 1 - 25 % |
| Lamp types | Incandescent/halogen lamps, fluorescent lamps, Energy saving lamps, LEDs |
| Control output | 100 mA |
| Ouput light | DALI-interface according to IEC SN EN 62 386 for max. 50 DALI devices |
| Max. cable cross section | max. 2 x 2,5 mm² |
| Size of concealed housing | 55 mm |
| Switching output | DALI |
| Detection range | 50 m² (ø 8 m | 360°) |
| Detection angle | 360° |
| Ambient temperature | -15°C ... 50°C |
| Type of protection | IP 54 (when fitted) |
| Mounting height (A) | Sitting (S) | Diagonally (T) | Head on to (R) |
| 2 m | 5 m² | 2.5 m | 38 m² | 7 m | 5 m² | 2.5 m |
| 2.5 m | 7 m² | 3 m | 38 m² | 7 m | 7 m² | 3 m |
| 3 m | 13 m² | 4 m | 50 m² | 8 m | 13 m² | 4 m |
| 3.5 m | 13 m² | 4 m | 50 m² | 8 m | |
| 4 m | 13 m² | 4 m | 64 m² | 9 m |
| Tender text | DOC | theRonda S360-110 DALI UP (65,0 kB) |
| Operating instructions | theRonda 110 DALI (2,1 MB) | |
| CAD symbol | ZIP | theRonda S360-110 DALI (39,9 kB) |
| CAD symbol | ZIP | theRonda P360 DALI (26,3 kB) |
| Data sheet | theRonda S360-110 DALI UP WH (2,0 MB) | |
| Brochure | Pre-assembled presence and motion detectors 2016 (306,1 kB) | |
| Catalogue | General catalogue 2024 (25,6 MB) | |
| BIM data | Open planning data in web app |
Your documents basket contains 0 items