                                                | Operating voltage | 230 V AC, 50 Hz | 
| Frequency | 50 Hz | 
| Stand-by consumption | 1.6 W | 
| Width | 4 modules | 
| Installation type | DIN rail | 
| Type of connection | Screw terminals | 
| Max. cable cross section | Solid wire: 0.5 mm² (Ø 0.8) to 6 mm² | Stranded wire with end sleeve: 0.5 mm² to 4 mm² | 
| Number of channels | 2 | 
| Type of contact | NO contact, 16 A, 10 A | 
| Opening width | < 3 mm | 
| Switching output | Potential-free | 
| Voltage output | 230 V AC | 
| Frequency output | 50 Hz | 
| Inrush current | 400 A (150 µs), 200 A (600 µs) | 
| Resistive load | 3680 W | 
| Incandescent/halogen lamp load | 2500 W | 
| Capacitive load | 140 µF | 
| Voltage input | 1 - 10 V | 
| Signal current input max. | 100 mA | 
| Signal duration | Continuous | 
| Max. cable length | 500 m | 
| Ambient temperature | -5°C ... 45°C | 
| Type of protection | IP 20 | 
| Protection class | II according to EN 60 730-1 | 
                            | Tender text | DOC | SME-2-S-KNX_4910274 (24,6 kB) | 
| Hand book | SMG2_SMG2S_V1_1_1101 (443,1 kB) | |
| Operating instructions | KNX-SMG-2-S_SME-2-S (392,1 kB) | |
| CAD symbol | ZIP | CAD_SME2SKNX (111,9 kB) | 
| KNX overall database KNXprod | ZIP | KNXprod (22,1 MB) | 
| Data sheet | SME 2 S KNX (219,6 kB) | |
| Catalogue | General catalogue 2024 (25,6 MB) | 
Your documents basket contains 0 items