IP Router KNX


  • Router/Interface/Line Coupler IP and KNX
  • Support of full Filter Table for all main groups 0…31
  • Monitoring for KNX bus voltage failure (KNX IP Service)
  • Unicast: Up to 10 unicast devices
  • Tunneling: Up to 5 Tunneling Server (Visualisation, App…)
  • Firmware update (Theben IP Tool Software)
  • Power Supply: 12–30 V DC/PoE - IEEE 802.3af class 1

Technical data

Operating voltage KNX Bus voltage, ≤10 mA
Operating voltage 12 – 30 V DC
Width 2 modules
Installation type DIN rail
Type of connection Bus connection: KNX bus terminal| RJ45 for LAN
Ambient temperature -5 °C … +45 °C
Stock temperature -25 °C … +55 °C
Protection class II according to EN 60 730-1
Type of protection IP 20